Huawei PowerCube 5000 Installation Manual page 80

Hide thumbs Also See for PowerCube 5000:
Table of Contents

Advertisement

PowerCube 5000 (SUN2000-150KTL-S0)
Installation Guide
Path
4.
Table 9-4 Setting the System Param. 2
Path
Settings Wizard
For example: If battery routes 1 and 2 are respectively connected to a battery string (a
battery string consists of 192 2 V, 800 Ah batteries in series), set Single-String Rated
Capacity (Ah) to 800 and Quantity of Battery String to 2.
5.
Table 9-5 Setting the System Param. 3
Path
Settings Wizard
Issue 03 (2020-04-10)
Set the System Param. 2.
Set the System Param. 3.
Parameters
Output Volt Level (V)
Output Volt Adjust (V)
Copyright © Huawei Technologies Co., Ltd.
Parameters
DG Number
Parameters
Batt. String Qty.
Battery Cell Num
Single-String Cap (Ah)
Number of Cabinet's HSU
System Start Min Capacity
Pct (%)
Setting
Set based on site requirements.
NOTE
Configurable level: 380/400/415
Set based on site requirements.
9 Power-on and Commissioning
Setting
Volt Li Batt and others
0/1
Setting
Set based on site
requirements.
NOTE
Configurable range: 0 – 10
Set based on site
requirements.
NOTE
Configurable range: 192 – 288
Set based on site
requirements.
NOTE
Configurable range: 0 – 7000
Set based on site
requirements.
NOTE
Configurable range: 1– 5
Set based on site
requirements.
NOTE
Configurable range: 0 – 100