Resetting procedure
C Controller module can be reset by operating the switch by the following procedure.
Do not reset the C Controller module during initialization.
Perform the initialization again if the module has been reset in error.

Setting parameters

Set parameters for the C Controller module.
Parameter: Setting data required for a C Controller system to operate. Set modules and a network in CW
Configurator for the C Controller module.
Connecting the C Controller module to the personal computer
Connect the CH1 on the C Controller module to the personal computer using an Ethernet cable.
Personal computer
Precautions
The IP address of the C Controller module and that of the personal computer must be set to the same segment. Since this
guide uses the default IP address for the C Controller module (192.168.3.3), set the IP address for the personal computer to
'192.168.3.* (*: except for 0, 3, and 255)'.
Set the subnet mask for the personal computer to '255.255.255.0'.
For how to change an IP address, refer to the following manual.
MELSEC iQ-R C Controller Module User's Manual (Application)
1.
2.
(2)
3.
(1)
C Controller
module
Hold the RESET/STOP/RUN switch (1) in the RESET
position.
Check that all LEDs turn OFF after the ERROR LED (2)
flashes several times.
Release the RESET/STOP/RUN switch (1) and put it
back to the STOP position.
2 USING C CONTROLLER MODULE
11
2.3 Setting the Module