NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Parameter
Hot aisle
temperature
and
humidity
sharing
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step 1
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
If the teamwork control succeeds, the teamwork topology of the smart cooling
product in the group is displayed, as shown in
note for the screen.
Figure 4-7 Teamwork topology
Table 4-7 Notes for the screen
No.
1
2
Issue 03 (2020-08-30)
Description
When this parameter
is enabled, the smart
cooling product,
which is not
configured with the
hot aisle T/H sensor
in the group, is
logically controlled by
using the acquired
value of the
configured hot aisle
T/H sensor.
and
Step
2.
Parameters
Note
On/Off
On indicates that the smart cooling product is started and
Off indicates that the smart cooling product is shut down.
01, 02, 03
Indicates the device address. The minimum address is the
master one and the rest are all slave ones.
NOTE
If the master one offline, the online device with the smallest
address is selected to be the new master.
Copyright © Huawei Technologies Co., Ltd.
Configuration
Principle
This parameter can be
enabled when there are
at least two smart
cooling products in the
group are configured
with hot aisle T/H
sensors.
Figure
4-7.
Table 4-7
4 Commissioning
Default
Value
Disable
.
describes the
97