Huawei NetCol5000-C030H90D0 User Manual page 164

In-row chilled water smart cooling product
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Exercise caution because the device is still energized after it is shut down on the
LCD.
Step 2 Open the front door.
Step 3 Use a Phillips screwdriver to loosen the R-shaped pipe clip that secures the supply
air temperature sensor on the front door post, and remove the supply air
temperature sensor probe.
Figure 6-11 Position of the supply air temperature sensor (NetCol5000-C065)
Figure 6-12 Position of the supply air temperature sensor (NetCol5000-C030/
C032)
Step 4 Remove the waterproof connector from the temperature sensor cable and remove
the supply air temperature sensor probe.
Step 5 Secure the new supply air temperature sensor cable to the original position using
cable ties, and fix the sensor probe using the R-shaped pipe clip.
Issue 03 (2020-08-30)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
156