Connecting The T/H Sensor Outside The Cabinet - Huawei NetCol5000-C030H90D0 User Manual

In-row chilled water smart cooling product
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)

3.12.6 Connecting the T/H Sensor Outside the Cabinet

Context
T/H sensors outside the cabinet are configured to detect the temperatures of
cold/hot aisles. They can be flexibly installed on the server cabinet based on onsite
situation. It is recommended that the T/H sensors be deployed near heat sources
in the hot aisle, or in places which lacks cooling air in the cold aisle. The T/H
sensors outside the cabinet must be near the smart cooling product to sense the
temperature of the outlet air, and must be away from the air exhaust vents of
other smart cooling products
Procedure
Step 1 Connect the T/H sensors outside the cabinet and the T/H sensors at the return air
side in series.
Figure 3-57 Cables routed outside the cabinet (NetCol5000-C065)
Issue 03 (2020-08-30)
Figure 3-57
or
Figure 3-58
Copyright © Huawei Technologies Co., Ltd.
shows how to route the cables.
3 Installation
73