NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Menu
Teamwor
k
Settings
System
Optional
Parts
Issue 03 (2020-08-30)
Parameter
Teamwork group
No.
Air conditioner
address
Teamwork function
Networking mode
Cold aisle sensor 1–
5
Copyright © Huawei Technologies Co., Ltd.
Description
Configuration Principle
Set the assigned
The number of the
teamwork
teamwork controlled
control number.
group, which is the same
for all the devices in the
group.
Set the assigned
Air conditioner addresses
unit address.
should be different from
each other.
Disable or
Set this parameter based
enable the
on the onsite device heat
teamwork
distribution.
function. If the
teamwork
function is
disabled, this
device is
operating
according to its
own control. If
the teamwork
function is
enabled, this
device works in
harmony with
others that in
the same group.
Networking
Networked over CAN or
mode for the
MAC_CAN. CAN network
teamwork. The
indicates teamwork control
networking
over a CAN bus, MAC_CAN
mode set on the
network teamwork control
screen must be
over an FE port.
consistent with
the actual
networking
mode.
Otherwise, the
teamwork
control function
will be
unavailable.
Cold aisle
If a T/H sensor outside the
sensors can be
cabinet is deployed in the
set to Enable or
cold aisle, enable the T/H
Disable.
sensor.
4 Commissioning
81