Huawei NetCol5000-C030H90D0 User Manual page 90

In-row chilled water smart cooling product
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Menu
System
Settings
Issue 03 (2020-08-30)
Parameter
Hot aisle sensor 1–
5
Cold aisle
temperature and
humidity sharing
Hot aisle
temperature and
humidity sharing
Dual power supply
setting
Altitude
Copyright © Huawei Technologies Co., Ltd.
Description
Configuration Principle
Hot aisle sensors
If a T/H sensor outside the
can be set to
cabinet is deployed in the
Enable or
hot aisle, enable the T/H
Disable.
sensor.
When this
Disable
parameter is
enabled, the
smart cooling
product, which is
not configured
with the cold
aisle T/H sensor
in the group, is
logically
controlled by
using the
acquired value
of the
configured cold
aisle T/H sensor.
When this
Disable
parameter is
enabled, the
smart cooling
product, which is
not configured
with the hot
aisle T/H sensor
in the group, is
logically
controlled by
using the
acquired value
of the
configured hot
aisle T/H sensor.
Primary power
Retain the default value.
first, or Primary
power first can
be set as
required.
Set the
-
parameter
according to the
actual situation.
4 Commissioning
82