NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Figure 2-10 Positions of NetCol5000-Cs in a container data center
(1) Server

2.7 Application Conditions

● If the water inlet temperature exceeds 10°C or the total load is less than 30%
of the cooling capacity of a single smart cooling product, the humidity may be
high. The customer is advised to add a dehumidifier (engineering
procurement).
● Do not install the smart cooling product near a noise-sensitive place such as an
office or a conference room.
Pipe Ports
The following table describes the ports reserved on the device.
Table 2-2 Pipe Ports
Item
Water outlet pipe
Water inlet pipe
(Optional) Humidifier water
inlet pipe
Automatic drainpipe
Issue 03 (2020-08-30)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
(2) NetCol5000-C
NetCol5000-C065
G 1–1/2inch port with
inner threads
G 1–1/2inch port with
inner threads
G 3/4inch port with
outer threads
BSPP 1/2inch port with
inner threads
2 Product Description
NetCol5000-C030/
C032
G 1inch port with
inner threads
G 1inch port with
inner threads
G 3/4inch port with
outer threads
BSPP 1/2inch port with
inner threads