Huawei NetCol5000-C030H90D0 User Manual page 92

In-row chilled water smart cooling product
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Menu
T/H
sensor
Issue 03 (2020-08-30)
Parameter
In-cabinet water
overflow alarm
action
Temperature and
humidity control
type
Temperature
setpoint
Copyright © Huawei Technologies Co., Ltd.
Description
Configuration Principle
Based on site,
Retain the default value.
set the device
action to
Shutdown,
Inactivity, Only
indoor fan
running, or
Humidification
stopped after
the floor
overflows.
Cold aisle, Hot
● When the application
aisle, Return
air, or Supply
air can be set as
required. The
temperature and
humidity set
points
correspond to
the selected
control type can
● When the application
be set.
● Hot aisle is not
After the
Set this parameter as
Temperature and
required.
humidity control
● Return air temperature:
type and the
temperature
● Supply air temperature:
value under this
type are set, the
● Cold aisle temperature:
device conducts
cooling or
heating based
● Hot aisle temperature:
on the settings.
4 Commissioning
scenario is cold or hot
aisle containment, you
are advised to choose
Cold aisle if the cold
aisle T/H sensors are
configured, and choose
Supply air if the cold
aisle T/H sensors are
not configured.
scenario is non-aisle
containment, you are
advised to choose
Return air, and choose
Cold aisle if the cold
aisle T/H sensors are
configured.
recommended.
26–35°C recommended
18–24°C recommended
18–24°C recommended
26–35°C recommended
84