Calibrating A Sensor; How To Modify A Password - Huawei NetCol5000-C030H90D0 User Manual

In-row chilled water smart cooling product
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
Figure 7-14 Performance Maint screen
Step 2 Tap Clear of a specific performance parameter to clear its runtime.
----End

7.1.11 Calibrating a Sensor

Context
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates
from the actual value. For example, if the return air temperature measured by
other temperature detection devices at the return air detection point is 20°C while
the value measured by the sensor is 22°C, the sensor has an error of 2°C, and the
calibration value should be set to –2°C.
Procedure
Step 1 On the home screen, choose Maint > Sensor Calibration.
Step 2 Fill the calibration value based on the measured error.
----End

7.1.12 How to Modify a Password

Prerequisites
Procedure
Step 1 On the home screen, choose Settings > User Settings to enter the User Settings
screen, as shown in
Issue 03 (2020-08-30)
To modify a password, log in as the admin user or operator user.
You can only modify the password of the current user.
Figure
Copyright © Huawei Technologies Co., Ltd.
7-15.