Connect and wire to shunt and alarms.
J1 is a 6-pin connector provided for analog interface to a plant shunt, distribution alarms, and open battery
string alarms. Typically, a factory installed plant wire harness plugs into this connector. This wire set has a
purple wire with a Faston ® receptacle for connecting the Open String Alarm from field installed battery
disconnect breakers.
Table 4 Analog Interface Connector Signals – Pulsar Plus
1
Pin
1
2
3
4
5
6
Connect and wire to VT-Probe, external ambient probe, or Remote Voltage Monitor.
2
J2 is an RJ-45 receptacle for connecting to 1-Wire devices.
850050111
Issue 03 August 2017
Action – Pulsar Plus
Analog Interface Connector
Signal
Shunt+
Shunt Reference
Shunt-
Fuse Alarm Major +24V
Open String
Fuse Alarm Major -48V
1-Wire Peripheral Connector
H5692448