Step
Connect and wire auxiliary inputs as required to Connector J3. J3 is an auxiliary input connector.
Utilize cable as necessary to obtain the desired connections to the inputs shown below.
Input Alarm Cable comcodes for J3 are: 50 ft.: CC848817651, 150 ft.: CC848817668.
Pin
Wire
1
BK
2
BR
3
R
4
O
3
5
Y
6
G
7
BL
8
V
9
S
10
W
18
Inputs are reconfigured for specific use for specific Eco applications.
850050111
Issue 03 August 2017
Action – Pulsar Plus
Auxiliary Input Connector

Table 5 Auxiliary Input Connector Signals - Pulsar Plus

18
Signal Name
Description
Aux Input 1
Auxiliary input to monitor a contact closure or open to its respective
return on pin 8, Auxiliary Input Return.
(Aux1)
Aux Input 2
Auxiliary input to monitor a contact closure or open to its respective
return on pin 8, Auxiliary Input Return.
(Aux2)
Auxiliary input to monitor a contact closure to the non-grounded
side of a dc bus (±24V/-48V) to create the standard Auxiliary Power
Aux Power
Major alarm.
Major Input
(AMJ)
Generator Running in Eco applications.
Plant Battery
Dedicated input to be monitored for a contact closure to its
Test/ Group
respective return on pin 9, Plant Battery Return. This signal is used
Standby/TR
for the Plant Battery Test and Group Standby Feature.
(GSTR)
Emergency
Dedicated EPO input to be monitored for a contact closure to its
Power Off
respective return on pin 10, Emergency Power Off Return.
(EPO)
Aux Input 3
Auxiliary input to monitor a contact closure or open to its respective
return on pin 8.
(Aux3)
Aux Input 4
Auxiliary input to monitor a contact closure or open to its respective
(Aux4)
return on pin 8.
Aux Input
Return
Return for Auxiliary Inputs 1-4.
(Aux_R)
Plant Battery
Test/Group
Return for Plant Battery Test and Group Standby.
Standby/TR
Ret.(GSTR_R)
Emergency
Power Off Ret.
Return for EPO input.
(EPO_R)