Wiring Of The Power Supply Module; Frame Ground Terminal (Fg) - Toshiba V Series User Manual

Sequence controllers
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

Chapter 4 Installation and Wiring
4
146

Wiring of the power supply module

PS693 (100-240Vac)
24V output
24 Vdc
(Sum of the internal
3.3V/5V output and 24V
0V
output should be under
35V. Do not connect the
output to other power
RUN contact
line.)
Output
Input power supply
100-240 Vac
*1
PS652 (100-110Vdc)
RUN contact
output
Input power supply
100-110Vdc(PS652)
*1
∗ 1 Line Filter Ground Terminal (LG).
5000 PF or less
Input Power Supply
5000 PF or less
LG

*2 Frame Ground Terminal (FG)

Connected to the unit base frame. Grounding terminal.
PS691 (100/200Vac)
NC
Input power supply
100-120Vac or
200-240Vac
L
N
LG
FG
*2
PS632 (24Vdc)
NC
NC
Input power supply
NC
24 Vdc(PS632)
LG
FG
*2
Usually the LG and FG terminals are shorted before
grounding.. However, the LG terminal may be open or
used for dedicated grounding, depending on the
environmental condition (such as leak current or
when the power supply system is grounded
elsewhere)
model 2000 Sequence Controller S2 User's Manual -Basic Hardware-
NC
NC
RUN contact
output
100Vac:short
200Vac:open
L
N
LG
FG
*1
*2
NC
NC
RUN contact
output
NC
LG
FG
*1
*2

Advertisement

Table of Contents
loading

This manual is also suitable for:

2000

Table of Contents