7.4.8 Logic outputs

A6V11899867_en--_a
The PT2002-A1 provides 4 logic outputs. They are open collector transistors
switching to GND.
The 4 logic outputs can be used to switch lamps, relays or other devices with a
current draw of max. 200mA.
The output can be powered with the DC 10 V provided on pin 12 of the connector,
or with a voltage of max. DC 36 V.
The logic output 1 and 2 are occupied by the PT2002-A1.
Logic outputs connector - 'CN3'
Pin
Description
1
Analog input 1
2
Analog input 2
3
Analog input 3
4
Analog input 4
5
Analog input 1
6
Analog input 2
7
Logic output 1
8
Logic output 2
9
Logic output 3
10
Logic output 4
11
GND
12
10 V

Table 87: PT2002-A1 logic outputs connector - 'CN3'

For more information, see Use analog control inputs [➙ 56] and Use logic
control output [➙ 82].
Connect external components
Fire brigade call station (AT) PT2002-A1
Remark
The analog control input cannot be used as
the logic output.
The analog control input cannot be used as
the logic output.
The analog control input cannot be used as
the logic output.
The analog control input cannot be used as
the logic output.
The analog control input cannot be used as
the logic output.
The analog control input cannot be used as
the logic output.
Occupied by the PT2002-A1
Occupied by the PT2002-A1
-
-
-
-