5 Power supply and batteries

5.1 Power supply in PC1001

5.1.1 Installation

A6V11899867_en--_a
Only one battery block can be installed in the PC1001-A3 or PC1002-A3 wall
mount cabinet. It is buffered via the power supply.
General guidelines
Do not connect the batteries after installation; instead, connect them immediately
before commissioning starts.
The batteries must be mounted in a leak-proof manner.
The batteries can be attached to the cabinet with a battery mounting kit. The
battery mounting kit is included in the scope of delivery.
The 'Voice alarm panel Compact 400' PC1001-A3 uses a Merawex power supply
ZM24V24A-600PZ. It is mounted and pre-assembled in the cabinet with the
following connections:
230 V screw terminals connection
Temperature sensor input
1x DC 24 V output for supplying power to the digital audio matrix board
1x screw terminal for 1x 24 V battery bank
3x connections with potential-free relay contacts for supply system and battery
monitoring

Fig. 34: PC1001-A3 power supply connectors

T
Connector for temperature sensor cable
F
Battery fuse 32 A slow
The battery connection cables must be as short as possible.
The temperature sensor must be positioned directly next to the batteries.
Power supply and batteries
Power supply in PC1001
5