Mounting/Installation; Mount The Cabinet; Fig. 1: Pc1001-A3 Position Of The Screws - Siemens Cerberus PACE Compact Installation, Mounting

Public address and controlled evacuation
Hide thumbs Also See for Cerberus PACE Compact:
Table of Contents

Advertisement

Mounting/Installation

4

Mount the cabinet

4 Mounting/Installation
4.1 Mount the cabinet
The 'Voice alarm panel Compact 400' PC1001-A3 and the 'Voice alarm panel
Compact 1000' PC1002-A3 cabinets are mounted on the wall with 4 screws. A
position for the cabinet should be defined. All peripheral cable entrances are on the
top of the cabinet.
A wall which can support heavy loads should be selected. The maximum weight of
the cabinet, with 100 Ah batteries, is about 140 kg.
The enclosed drilling jig is used to mark the holes for the anchors. Use the correct
anchors for your kind of wall.
Make sure that the batteries are not installed during the mounting.
At least 2 people are needed to lift the cabinet in the right position and screw it to
the wall.
The batteries are inserted only when the cabinet is secured on the wall.
The figure below indicates the delivery state of the 'Voice alarm panel Compact
400' PC1001-A3 cabinet with the door open (the 'Voice alarm panel Compact 1000'
PC1002-A3 cabinet is similar). The digital audio matrix board with some daughter
boards and 2 amplifiers PV1001-A1, the power supply, some connectors and cable
trays are pre-installed in the cabinet.
Optional components with DIN rail connectors are mounted in the DIN rail area on
the left side of the cabinet.

Fig. 1: PC1001-A3 position of the screws

A6V11899867_en--_a