Operating unit and call stations PT1002-A1

6.2 Operating unit and call stations PT1002-A1

6.2.1 Mounting

70 | 122
The 'System operating unit and call station' PT1002-A1 is designed to be mounted
on a front door of a Cerberus PACE Compact cabinet.
Use the provided cables and 'Call station interface (RS485)' PTO2008-A1 to
connect the PT1002-A1.
The 'System operating unit and call station' PT1002-A1 is designed to be mounted
on a front door of a Cerberus PACE Compact cabinet in place of the mounted blind
plate.

Fig. 39: PT1002-A1 unmount front door blind plate

1. Take off the earth connection at the blind plate of the Cerberus PACE Compact
cabinet font door.
2. Unscrew the 8 screws of the blind plate.
3. Remove the blind plate.
4. Insert the PT1002-A1.
5. Use the 8 screws to mount the PT1002-A1.
6. Mount earth connections on the top and bottom of the PT1002-A1 to the
cabinet door.
7. Mount the delivered PTO2008-A1 at the DIN rail of the cabinet.
8. Print and insert inscription stripes.
9. Configure and install the PT1002-A1.
A6V11899867_en--_a