Pin
Description
1
TX+
2
TX-
3
RX+
4
RX-
5
NC
6
Shield
Pin
Description
1
D1+/TX+
2
D1-/TX-
3
D2+/RX+
4
D3+
5
D3-
6
D2-/RX-
7
D4+
8
D4-
A6V11899867_en--_a
Ethernet in connectors - 'CN1' and 'CN3'
Remark: when used in a 2x4 wire cable
CAT5 pin
CAT5 according to T568B
1
White/orange
2
Orange
3
White/green
6
Green
-
Do not connect
-
Shield

Table 95: PTO2009-A1 Ethernet in connectors - 'CN1' and 'CN3'

Ethernet out RJ45 connectors - 'J1' and 'J2'
Remark: when used in a 2x4 wire cable
CAT5 pin
CAT5 according to T568B
1
White/orange
2
Orange
3
White/green
6
Blue
-
White/blue
-
Green
-
White/brown
-
Brown

Table 96: PTO2009-A1 Ethernet out RJ45 connectors - 'J1' and 'J2'

Fault relay connector - 'CN6'
Pin
Description
1
10 V
2
A-24 V
3
B-24 V

Table 97: PTO2009-A1 fault relay connector - 'CN6'

Connect external components
Call station interface (redundant) PTO2009
Fire alarm cables color code
according to VDE0815
Grey
Yellow
Brown
Green
Do not connect
Shield
Fire alarm cables color code
according to VDE0815
Grey
Yellow
Brown
Red
Blue
Green
White
Black
Remark
10 V reference
Closed if 'Power In A', 'CN2' has a fault
Closed if 'Power In B', 'CN4' has a fault
7
119 | 122