Install relay outputs

4.21.1 Use analog control inputs

4.22 Install relay outputs
56 | 122
The analog control inputs measure the voltage between GND and DC 10 V.

Fig. 30: Use of analog control inputs

A variable linear resistor 10 k potentiometer with at least 0.05 W (1/20 W) is
required for this function.
The resistor is connected between GND and 10 V. The wiper is connected to an
analog control input.
The PC1001-A3 and PC1002-A3 Cerberus PACE Compact digital audio matrix
boards both provide 8 connectors ('1-DO' to '8-DO') with 8 relay outputs in the logic
out area.
The relay outputs are used to activate LEDs or to communicate a status change of
the system.
The relay contacts can switch a voltage of up to 48 V.

Fig. 31: Relay outputs connectors

Relay outputs connectors - '1-DO' to '8-DO'
Pin
Description
1
NC
2
C
3
NO

Table 26: Relay outputs connectors - '1-DO' to '8-DO'

Remark
Normally closed
Common
Normally open
Function
Regularly closed. Open when
activated
Middle contact
Regularly open. Closed when
activated