Failure Diagnosis for Inverter System

4.

Failure Diagnosis for Inverter System

4.1

Points of Diagnosis

The main causes for each malfunction code are given in the table below. (For details refer to the next page
and those following.)
• : Failure is probable
{ : Failure is possible
... : Failure is improbable
— : Failure is impossible
Malfunction
192
Contents of
Inverter
code
malfunction
PC board
power unit
L4
Radiator fin
...
temperature
rise
L5
Instantaneous
{
over-current
L8
Electronic
...
thermostat
L9
Stall
...
prevention
LC
Malfunction of
transmission
between
{
inverter PC
board and
outdoor unit
PC board
U2
Abnormal
current/
{
voltage
P1
Over-ripple
protection
{
P4
Defect of
radiator fin
{
temperature
sensor
Location of failure
Compressor
Refrigerant
system
Other
...
{
{
{
{
...
Troubleshooting Urban Multi "MX1, ME1 Series" Using R-22
PACD011001C2
Outdoor
Other
Field
Point of diagnosis
unit PC
cause
board
Is the intake port of
...
the radiator fin
clogged?
Inspect the
compressor.
Inspection the
compressor and
refrigerant system.
Inspection the
compressor and
refrigerant system.
Inspect the
connection between
the inverter PC
...
board and outdoor
unit PC board.
Next, inspect the
inverter PC board.
• Inspect the fuse
on the inverter PC
...
board.
• Check the DC
voltage.
• Open phase
• Current/voltage
{
imbalance
• Defect of main
circuit wiring
Inspect the radiator
fin thermistor.