Panasonic Urban Multi MX1R Series Service Manual page 362

Using r-407c / r-22
Table of Contents

Advertisement

PACD011001C2
Mode No
Function
40
Malfunction hysteresis
display
41
Display of sensor and
address data
43
Forced fan ON
44
Individual setting
45
Unit No. transfer
46
This function is not used by UM "MX1R Series".
47
Troubleshooting Urban Multi "MX1R, ME1R Series" Using R-407C
Contents and operation method
Display malfunction hysteresis.
The hysteresis No. can be changed with the
button.
Display various types of data.
Select the data to be displayed with the
Sensor data
0: Thermostat sensor in remote controller.
1: Suction
2: Liquid pipe
3: Gas pipe
Address data
4: Indoor unit address
5: Outdoor unit address
6: HR box address
7: Zone control address
8: Cool/heat group address
9: Demand / low noise address
Manually turn the fan ON by each unit. (When you
want to search for the unit No.)
By selecting the unit No. with the
can turn the fan of each indoor unit on (forced ON)
individually.
Set the fan speed and air flow direction by each unit
Select the unit No. with the time mode
Set the fan speed with the
Set the air flow direction with the
Transfer unit No.
Select the unit No. with the
Set the unit No. after transfer with the
Troubleshooting by Remote Controller
Remote controller display example
Unit 1
Malfunction code
(VE007)
button.
Sensor data display
Address display
(VE008)
Unit 1
button, you
(VE009)
button.
Unit 1
button
button.
Fan speed 1: Low
3: High
(VE010)
button.
button.
Unit
(VE011)
40
2-U4
Malfunction code
Hysteresis No: 1 - 9
1: Latest
Unit No.
Sensor type
41
1 1
2 7
Temperature ºC
Unit No.
Address type
41
1 8
1
Address
43
Code
44
1 3
Air flow direction
P0 - P4
Present unit No.
45
1
0 2
Code
Unit No. after
transfer
341