Interface Adaptor; Bms Interface Adaptor For Unified Group (Krp2A51·52) - Panasonic Urban Multi MX1R Series Service Manual

Using r-407c / r-22
Table of Contents

Advertisement

Interface Adaptor

6. Interface Adaptor

6.1
BMS Interface Adaptor for Unified Group (KRP2A51·52)
Various remote control (remote control mode, remote temperature setting, display of operation, display of
malfunction) can be carried out by mounting this optional accessory in the indoor unit. Up to 64 groups of
indoor units can be monitored and controlled all at once by one adaptor PC board. The BMS interface
adaptor for unified group cannot however be used in combination with other optional controllers for
centralised control (central remote controller, unified on/off controller, schedule timer, etc.).
6.1.1
Outline of System
1. Individual control (controls indoor units individually)
2. Group control (Simultaneously controls group-controlled indoor units [max. 16 units] all together)
‹ In the case of individual display, install a BMS interface adaptor PC board for unified group in the indoor
3. Zone control
598
unit.
Simultaneously controls up to 64 groups consisting of up to 16 group-controlled indoor units each all
together (max. 64 groups × 16 units = 1,024 units).
PACD011001C2