Compressor Capacity Control - Panasonic Urban Multi MX1R Series Service Manual

Using r-407c / r-22
Table of Contents

Advertisement

Function
1.17

Compressor Capacity Control

CU-5
Pressure is sampled every 20 seconds by pressure sensor, and the inverter compressor is controlled in 13
stages by microcomputer.
Frequency range: 34 - 116 Hz (13 stages) and common for 50/60Hz area.
CU-8·10
Pressure is sampled every 20 seconds by pressure sensors, and the inverter + standard compressor is
controlled in 20 stages by microcomputer.
262
Min. output
Frequency
32Hz
34Hz
38Hz
42Hz
48Hz
54Hz
60Hz
68Hz
76Hz
86Hz
96Hz
106Hz
116Hz
Max. output
(M019)
Commercial power supply
compressor (off)
Frequency
32Hz+OFF
34Hz+OFF
38Hz+OFF
42Hz+OFF
48Hz+OFF
54Hz+OFF
62Hz+OFF
68Hz+OFF
76Hz+OFF
86Hz+OFF
96Hz+OFF
106Hz+OFF
Commercial power supply
compressor (full load)
Frequency
38Hz+ON
48Hz+ON
62Hz+ON
76Hz+ON
86Hz+ON
96Hz+ON
106Hz+ON
116Hz+ON
Function Urban Multi "MX1R, ME1R Series" Using R-407C
PACD011001C2
Min. output
Max. output
(VE005)