1.3.2
Allowed Range of Indoor Unit and HR Box Connection
Range A
Range B
HR box
Range C
Indoor unit
„ Arrange systems to conform below conditions referring to above diagram.
Range
Range A Total indoor unit capacity
Range B Total indoor unit capacity
Range C Total indoor unit capacity
8
Item
allowed for simultaneous
cooling/heating operations
allowed for connection to HR box
General Information Urban Multi "MX1, ME1 Series" Using R-22
Range C
Range C
Range C
Model of outdoor
Total capacity of
unit and HR box
connectable indoor
units
CU-8ME1XPA
11.2 to 29.1kW
CU-10ME1XPA
14 to 36.4kW
CU-8ME1XPA
11.2kW or more
CU-10ME1XPA
14kW or more
CZ-100HR1HE
less than 11.2kW
CZ-160HR1HE
11.2 to 18kW
PACD011001C2
( Cooling
( Cooling
only unit )
only unit )
(M103)
Max. number of
connectable indoor
units
13 units
16 units
13 units
16 units
5 units or less
6 units or less