Panasonic Urban Multi MX1R Series Service Manual page 32

Using r-407c / r-22
Table of Contents

Advertisement

PACD011001C2
A. Compressor M1C
Scroll compressor that operates on 30~116Hz by inverter drive enables 13-step capacity control.
Capacity control is carried out for individual and linear control of indoor units.
B. Oil separator
The oil separator is a device that collects the oil discharged from the compressor.
The collected oil is constantly recycled to the compressor via capillary tube.
C. Solenoid valve (hot gas bypass) Y2S
Valve is opened by low pressure safety control when low pressure drops.
Balances high/low pressure when off in order to reduce load when the compressor starts.
D. Outdoor unit electronic expansion valve Y1E
Expansion valve when heating. Senses compressor suction pipe and low pressure equivalent saturated
temperature, and carries out superheat degree control.
E. Solenoid valve (injection) Y3S
Controls injection in order to prevent overheating.
F. Heat exchange pipe
Subcooling so that refrigerant drift doesn't occur between indoor units when flash gas is produced in the
liquid pipe.
G. Pressure sensor (high pressure, red) SENPH
Semiconductor pressure sensor for sensing the operating status of the indoor by refrigerant pressure which
senses discharge pressure.
H. Pressure sensor (low pressure, blue) SENPL
Semiconductor pressure sensor for sensing the operating status of the indoor by refrigerant pressure which
senses suction pressure.
Function Urban Multi "MX1, ME1 Series" Using R-22
Function
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents