Control During Low Outdoor Air Temperature Cooling

When the outdoor air temperature is low in cooling operation, outdoor unit fans, electronic expansion valve
and compressors are controlled as follows in order to primarily maintain high pressure and to protect drop
in refrigerant circulation caused by drop in high pressure.
CU-5
Operating status
Normal operation
Low outdoor temperature
cooling operation
CU-8·10
Operating status
Normal operation
Low outdoor temperature
cooling operation
Note:
Step No. changes according to high pressure, low pressure and frequency.
(Step No. increases with reduction of high and low pressure.)
Low Outdoor Air Cooling in Conditions (Steps 1-1, 2, 3)
Conditions satisfied
• EV = 2000 pulses
(completely open)
or
• High pressure < 14 kg/cm²
(1.372 MPa)
or
• Low outdoor air cooling IN
conditions (Step 2)
Function Urban Multi "MX1, ME1 Series" Using R-22
Electronic expansion valve
Step 1
Step 2
Electronic expansion valve
Step 1-1
Step 1-2
Step 1-3
Step 2
Normal operation
«
• Cooling with compressor running
(doesn't include oil return)
&
• High pressure < 10 kg/cm²
Step 1-1
«
carried out 30
continuous
seconds
Step 1-2
«
carried out 30
continuous
seconds
Step 1-3
Fan
Fully open
H
Fully open
L
Fully open
OFF
Fan
M1F M2F
Fully open
H
ON
Fully open
L
ON
Fully open
H
OFF
Fully open
L
OFF
Fully open
OFF OFF
¥
• EV = 2000 pulses
• High pressure > 14 kg/cm²
¥
carried out 30
continuous
seconds
¥
carried out 30
continuous
seconds
Function
Frequency (Hz)
Changes according to operating
status
76
48
Frequency (Hz)
CU-8
CU-10
Changes according to operating
status
96
116
86
106
76
96
60
76
(completely open)
or
(1.372 MPa)
(VF006)
45