3 DCC Blocks
SINAMICS
parameter
number
p22051
boBit1Limit
Speed
p22052
boBit2Limit
Speed
p22053
boPreLimit
Switch
p22054
rLimit1 [%]
p22055
rLimit2 [%]
p22056
rLimit3 [%]
p22057
rLimit4 [%]
p22058
rOutSpeedSetpoint
PLS [%]
NOTE
p22054 (PreLimitSwitch_rLimit1 [%]) must be 100. According to truth table on
page 32 of SIMOCRANE Drive-Based Technology, if Bit1Limitspeed,
Bit2LimitSpeed, and Bit3LimitSpeed are all false, then speed limit 1 (p22054) is
selected.
NOTE
p22057 (PreLimitSwitch_rLimit 4 [%]) is where desired pre-limit speed for
LimitSwitch is set, because when either positive or negative direction limit switch
is triggered, r21851 (LimitSwitch_boOut_ActivatePreLimitSwitch (p22053)) goes
high, activating the CraneDCC PreLimitSwitch logic.
Extended Crane Drive-Based Technology AC
Extended Crane Drive-Based Technology SINAMICS S120
DCC Add-On Description 109767457,
Name
Connection
type
IN
IN
IN
IN
IN
IN
IN
OUT
V1.2,
09/2019
Default
Data
assignment
type
0
BOOL
If using LimitSwitch from
ExtendedCraneDCC, this
can be left at 0
0
BOOL
If using LimitSwitch from
ExtendedCraneDCC, this
can be left at 0
0
BOOL
Connect to r21851
(LimitSwitch_boOut_
ActivatePreLimitSwitch
(p22053)) from
ExtendedCraneDCC
100
REAL
Leave default value of 100
50
REAL
If using LimitSwitch from
ExtendedCraneDCC, this
can be left at 0
25
REAL
If using LimitSwitch from
ExtendedCraneDCC, this
can be left at 0
5
REAL
Actual pre-limit speed used
for LimitSwitch block. Set
desired pre-limit speed.
0
REAL
If using LimitSwitch function
of ExtendedCraneDCC,
connect this to p1070 (CI:
Main setpoint) of drive axis.
Meaning
30