Setting Up Communication Between Pcm600 And The Ied - ABB Relion 670 Series Commissioning Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 403-UUS Rev. K
1
0
IEC04000310 V2 EN-US
Figure 2:
1 IED energized. Green LED instantly starts flashing
2 LCD lights up and "IED startup" is displayed
3 The main menu is displayed. A steady green light indicates a successful startup.
If the upper row in the window indicates 'Fail' instead of 'Available' and the green LED flashes, an
internal failure in the IED has been detected.
4.5

Setting up communication between PCM600 and the IED

The communication between the IED and PCM600 is independent of the communication protocol used
within the substation or to the NCC.
The communication media is always Ethernet and the used transport layer is TCP/IP.
Each IED has an RJ-45 Ethernet interface connector on the front. The front Ethernet connector is
recommended to be used for communication with PCM600.
When an Ethernet-based station protocol is used, PCM600 communication can use the same Ethernet
port and IP address.
To connect PCM600 to the IED, two basic variants must be considered.
Direct point-to-point link between PCM600 and the IED front port. The front port can be seen as a
service port.
A link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to enable communication.
The communication procedures are the same in both cases.
1.
If needed, set the IP address for the IEDs.
2.
Set up the PC or workstation for a direct link (point-to-point), or
3.
Connect the PC or workstation to the LAN/WAN network.
4.
Configure the IED IP addresses in the PCM600 project for each IED to match the IP addresses of
the physical IEDs.
Setting up IP addresses
Communication between the IED and PCM600 is enabled from the LHMI. The IP address and the
corresponding communication subnetwork mask must be set via the Ethernet configuration tool (ECT) for
each available Ethernet interface in the IED. Each Ethernet interface has a default factory IP address
when the IED is delivered. The IP adress and the subnetwork mask might have to be reset when an
additional Ethernet interface is installed or an interface is replaced.
Bay control REC670
Commissioning manual
2
t1
xx04000310-1-en.vsd
Typical IED start-up sequence
© 2017 - 2021 Hitachi Power Grids. All rights reserved
3
t (s)
t2
Section 4
Starting up
SEMOD58570-5 v15
41