Verifying Instantaneous Back-Up Trip At Cb Faulty Condition; Verifying The Case Functionmode = Cb Pos; Verifying The Case Retripmode = Contact - ABB Relion 670 Series Commissioning Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 403-UUS Rev. K
Checking the case BuTripMode = 2 out of 4
The ground-fault current setting Pickup_N may be equal to or below phase-current setting Pickup_PH.
1.
Set BuTripMode = 2 out of 4.
2.
Apply the fault condition, including initiation of CCRBRF (50BF), with one-phase current above set
Pickup_PH and residual (ground fault) above set Pickup_N.
3.
Verify that back-up trip is achieved after set time. If selected, re-trip should also appear.
4.
Apply the fault condition, including initiation of CCRBRF (50BF), with at least one-phase current
below set Pickup_PH and residual (ground fault) above set Pickup_N. The current may be
arranged by feeding three- (or two-) phase currents with equal phase angle (I0-component) below
Pickup_PH, but of such value that the residual (ground fault) current (3I
Pickup_N.
5.
Verify that back-up trip is not achieved.
6.
Disconnect AC and BFI_3P input signals.
11.4.9.7

Verifying instantaneous back-up trip at CB faulty condition

Applies in a case where a signal from CB supervision function regarding CB being faulty and unable to
trip is connected to input 52FAIL.
1.
Repeat the check of back-up trip time. Disconnect current and input signals.
2.
Activate the input 52FAIL. The output CBALARM (CB faulty alarm) should appear after set time
tCBAlarm. Keep the input activated.
3.
Apply the fault condition, including initiation of CCRBRF (50BF), with current above set current
value.
4.
Verify that back-up trip is obtained without intentional delay, for example within 20ms from
application of initiation.
5.
Disconnect injected AC and BFI_3P input signals.
11.4.9.8

Verifying the case FunctionMode = CB Pos

It is assumed that re-trip without current check is selected, RetripMode = UseFunctionMode.
1.
Set FunctionMode = CB Pos.
2.
Apply input signal for CB closed to relevant input or inputs 52A_A, 52A_B or 52A_C.
3.
Apply the input signal, or signals for the start of CCRBRF.
4.
Verify that phase selection re-trip and backup trip are achieved after set times.
5.
Disconnect the start signal(s). Keep the CB closed signal(s).
6.
Apply input signal(s), for start of CCRBRF.
7.
Arrange disconnection of CB closed signal(s) well before set backup trip time t2
8.
Verify that backup trip is not achieved.
11.4.9.9

Verifying the case RetripMode = Contact

It is assumed that re-trip without current check is selected, RetripMode = Contact.
1.
Set FunctionMode = Contact
2.
Apply input signal for CB closed to relevant input or inputs 52a_A (B or C).
3.
Apply input signal, or signals for initiation of CCRBRF (50BF).
4.
Verify that phase selection re-trip and back-up trip are achieved after set times.
Bay control REC670
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 11
Testing functionality by secondary injection
M12104-179 v7
) will be above set value
0
M12104-197 v7
GUID-06D1545D-31F7-4B48-821E-151212962A81 v1
M12104-213 v10
107