Circuit protection devices with communication and metering function

3.3 5SL6 COM miniature circuit breaker

3.3
5SL6 COM miniature circuit breaker
5SL6 COM miniature circuit breakers do not just protect final circuits like conventional
miniature circuit breakers during overload and short-circuits, they also gather information on
the status and the faults in the electric circuit.
They wirelessly communicate the measured values such as current, voltage, temperature, line
frequency, power, energy, operating hours, tripping operations and switching cycles to the
higher-level 7KN Powercenter 1000 data transceiver. Monitoring of the electric circuit
enables predictive error detection by reporting pre-warnings if, for example, the set limit
value of the current is exceeded.
The device only requires the external and N-conductor connection (230 V AC) and no
additional power supply (24 V DC) for the communication and metering function. With a
width of 1 TE, the 5SL6 COM miniature circuit breaker is as large as conventional, non-
communicating miniature circuit breakers. The 5SL6 COM is designed for nominal currents of
2 ... 32 A and available in the tripping characteristics B and C.
3.4

5SV6 COM arc fault detection device

With the communication-capable 5SV6 COM arc fault detection device, which has the
integrated function of a miniature circuit breaker, the affected final circuit can be protected
with regard to overload, short-circuit and fault arcs.
16
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01