Information Categories Of The Sentron Circuit Protection Devices - Siemens Sentron 7KN POWERCENTER 1000 Manual

Circuit protection devices with communication and measuring function
Hide thumbs Also See for Sentron 7KN POWERCENTER 1000:
Table of Contents

Advertisement

Functions
6.4 Modbus TCP connection
6.4.4

Information categories of the SENTRON circuit protection devices

The metering and communication-capable SENTRON circuit protection devices have different
categories of information.
Many of these are common to all or many devices. There is also information that is specific
for individual device types. In the following chapters this is marked with an "x" for all devices,
if the register is available. Furthermore, the scope of information can expand in other
versions.
The following categories are accessible to the applications via Modbus TCP.
Category
Description
Identification
Device characteristics according to manufacturer (e.g. order number, rated current, tripping charac-
teristic)
Usage environment (plant identifier, location identifier, installation date)
Communication
Parameters for communication path settings: Ethernet, Bluetooth, radio
parameters
Communication
MAC addresses and installation codes of the radio stations
information
Measured and state
Electrical measured variables (e.g. current, voltage, line frequency, power, energy),
variables
Temperature
Switching state
Measured value
Times for the averaging
settings
Limit monitoring
Alarm triggering thresholds
Expected energy flow direction
Diagnostics
Measured variables of the diagnostics functions (e.g. operating hours, switching cycles, tripping op-
erations)
Parameters for alarm and status information
This information can be displayed or changed with SENTRON powerconfig and the
SENTRON powerconfig app.
The following description is used to be able to access this with other applications and not just
with SENTRON applications such as powermanager, powermind, powerconfig, powerconfig
app and 7KN Powercenter 3000.
The information is described in the data point with register number, data format and access
possibility.
The accesses mean the following function codes:
• R: 0x03, 0x04
• RW: 0x03, 0x04 or 0x10
• WO: 0x10
• CMD: 0x06
66
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01