5Sv6 Com Arc Fault Detection Device - Siemens Sentron 7KN POWERCENTER 1000 Manual

Circuit protection devices with communication and measuring function
Hide thumbs Also See for Sentron 7KN POWERCENTER 1000:
Table of Contents

Advertisement

Designation
Measurable line frequency initial value
Power consumption of the power supply
Measuring category for voltage measurement
Minimum measurable current at AC
Maximum measurable current at AC
Radio regulations EU
Radio transmission frequency
Radio transmission power
10.4

5SV6 COM arc fault detection device

Designation
Order number
Product name
Product version
Tripping characteristic class
Operational current for AC rated value
Supply voltage for AC rated value
Supply voltage frequency rated value
Available measurement data
IP degree of protection
Design of electrical connection
Number of poles
Mounting type
Product expansion can be installed
Breaking capacity current acc. to EN 60898-1 rated value
Number of modular width units
Power loss [W] (max.)
Power loss [W] at rated value current with AC at warm oper-
ating condition per pole
Minimum supply voltage for testing equipment
Touch protection against electric shock according to EN
50274
Typical mechanical endurance (operating cycles)
Overvoltage category
Minimum connectable conductor cross-section, solid
Maximum connectable conductor cross-section, solid
Minimum connectable conductor cross-section, stranded
Maximum connectable conductor cross-section, stranded
Maximum connectable conductor cross-section, finely
stranded with end sleeve
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01
10.4 5SV6 COM arc fault detection device
Value
45 Hz
0.4 VA
CAT III acc. to IEC 61010-2-030
0.04 A
2 x I
r
2014/53/EU
2400 - 2483.5 MHz
10 dBm
Value
5SV6016-xMCyy (x= 6 or 7, yy= 06, 10, 13, 16, 20, 25, 32)
LS-combo 5SV6 COM arc fault detection device
Compact device
B and C
6 A, 10 A, 13 A, 16 A, 20 A, 25 A, 32 A
230 V
50 Hz
voltage, current, active power, apparent power, reactive
power, active energy, line frequency, power factor, tempera-
ture, switching cycles, operating hours, tripping operation,
warnings
IP20, with connected protective device and conductors
Screw connection
1P+N
DIN rail (REG)
Yes
6 kA
1
Between 1 ... 5.7 W depending on rated current and charac-
teristics
Between 0.9 ... 4.6 W depending on rated current and char-
acteristics
195 V
Finger and back-of-hand safe
10000
III
0.75 mm
2
16 mm
2
0.75 mm
2
16 mm
2
10 mm
2
Technical specifications