Siemens Sentron 7KN POWERCENTER 1000 Manual page 75

Circuit protection devices with communication and measuring function
Hide thumbs Also See for Sentron 7KN POWERCENTER 1000:
Table of Contents

Advertisement

Reg-
Length
Designation
ister
3652
1
Switching
Alarm1 on and
off for lower
voltage violation
3653
2
Limit value for
lower voltage
violation for
Alarm1
3655
2
Hysteresis for
lower voltage
violation Alarm1
3661
1
Switching
Alarm2 on and
off for lower
voltage violation
3662
2
Limit value for
lower voltage
violation for
Alarm2
3664
2
Hysteresis for
lower voltage
violation Alarm2
3670
1
Resetting the
energy counter
3674
1
Energy flow
direction
3675
1
Reset the ex-
treme values
3676
1
Switching the
alarm on and off
for low AFDD
trip threshold
violation
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01
For-
Value
Default
mat
range
U16
0 = Off
0
1 = On
FP32
150 ...
195
230
FP32
0 ... 10
10
U16
0 = Off
0
1 = On
FP32
150 ...
185
230
FP32
0 ... 10
10
U16
0x0815
U16
0 =
0
down→
up,
1 = up →
down
U16
0x0815
U16
0 = Off
1
1 = On
6.4 Modbus TCP connection
Unit
Ac-
POC
5ST3
cess
COM
1000
RW
-
-
V
RW
-
-
%
RW
-
-
RW
-
-
V
RW
-
-
%
RW
-
-
CMD
-
-
RW
-
-
CMD
-
-
RW
-
-
Functions
5SL6
5SV6
3NA
COM
COM
COM
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
x
x
-
x
x
-
x
x
-
-
x
-
73