Technical specifications
10.3 5SL6 COM miniature circuit breaker
Designation
Product standard leading
Supply voltage frequency rated value
Power loss [W] (max.)
Power loss [W] a rated value current with AC at warm oper-
ating condition per pole
Power loss [W] on N-pole at rated current at AC during oper-
ation
Vibration resistance according to IEC 60068-2-6
Product features touch protection
Position of network connection cable
Mounting position
Mounting depth
Height
Width
Depth
Net weight
Electrical endurance (operating cycles) at AC load on average 7500
Typical mechanical endurance (operating cycles)
Product feature silicone-free
Product feature halogen-free
Product feature sealable
Suitability for use amperemeter
Suitability for use reactive power meter
Suitability for use frequency meter
Suitability for use voltmeter
Suitability for use active power meter
Standard for shock
Standard for environmental testing sinusoidal vibrations
IP degree of protection, at rear
IP degree of protection, on the front
Reference condition for measuring accuracy
Formula for relative total measurement inaccuracy for
measured variable power factor
Formula for relative total measurement inaccuracy for
measured variable power
Formula for relative total measurement inaccuracy for
measured variable voltage
Formula for relative total measurement inaccuracy for
measured variable active power
Formula for relative total measurement inaccuracy for
measured variable reactive power
Measuring method for current measurement
Measuring method for voltage measurement
Maximum measurable mains voltage between N and L
Minimum measurable mains voltage between N and L
Measurable line frequency final value
90
Value
EN 60898-1
50 Hz
Between 1 ... 5.7 W depending on rated current and charac-
teristics
Between 0.9 ... 4.6 W depending on rated current and char-
acteristics
Between 0.02 ... 0.9 W depending on rated current and
characteristics
Yes
Yes
Any
Any
70 mm
90 mm
18 mm
76 mm
120 g
10000
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
IEC 61373
IEC 60068-2-6
IP20
IP40
in accordance with IEC 61557-12, IEC 62053-22 and
IEC 62053-23
+/- 0.5%
+/- 1%
+/- 0.5%
+/- 1%
+/- 1%
TRMS
TRMS
400 V
50 V
65 Hz
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01

Hide quick links:

Advertisement

Table of Contents
loading