Siemens Sentron 7KN POWERCENTER 1000 Manual page 94

Circuit protection devices with communication and measuring function
Hide thumbs Also See for Sentron 7KN POWERCENTER 1000:
Table of Contents

Advertisement

Technical specifications
10.4 5SV6 COM arc fault detection device
Designation
Minimum connectable conductor cross-section, finely
stranded with end sleeve
Minimum tightening torque
Maximum tightening torque
Pollution degree
Minimum ambient temperature during storage
Maximum ambient temperature during storage
Maximum ambient temperature during operation
Minimum ambient temperature during operation
Ambient temperature with 95% relative air humidity
Number of test cycles for environmental testing in accord-
ance with IEC 60068-2-30
Product feature silicone-free
Product feature halogen-free
Minimum tripping current at arcs serial to load
Maximum tripping current at arcs serial to load
Minimum tripping current at arcs parallel to load
Maximum tripping current at arcs parallel to load
Mounting position
Mounting depth
Height
Width
Depth
Net weight
Suitability for use amperemeter
Suitability for use reactive power meter
Suitability for use frequency meter
Suitability for use voltmeter
Suitability for use active power meter
Standard for shock
Standard for environmental testing sinusoidal vibrations
IP degree of protection, at rear
IP degree of protection, on the front
Reference condition for measuring accuracy
Formula for relative total measurement inaccuracy for
measured variable power factor
Formula for relative total measurement inaccuracy for
measured variable power
Formula for relative total measurement inaccuracy for
measured variable voltage
Formula for relative total measurement inaccuracy for
measured variable active power
Formula for relative total measurement inaccuracy for
measured variable reactive power
Measuring method for current measurement
Measuring method for voltage measurement
Maximum measurable mains voltage between N and L
92
Value
0.75 mm
2
1.2 N.m
2 N.m
2
-40°C
75°C
45°C
-25°C
55°C
28
Yes
Yes
2 A
Operating current
50 A
500 A
Any
70 mm
90 mm
18 mm
68.5 mm
120 g
Yes
Yes
Yes
Yes
Yes
IEC 61373
IEC 60068-2-6
IP20
IP40
in accordance with IEC 61557-12, IEC 62053-22 and
IEC 62053-23
+/- 0.5%
+/- 1%
+/- 0.5%
+/- 1%
+/- 1%
TRMS
TRMS
400 V