5St3 Com Auxiliary Switch And Fault Signal Contact - Siemens Sentron 7KN POWERCENTER 1000 Manual

Circuit protection devices with communication and measuring function
Hide thumbs Also See for Sentron 7KN POWERCENTER 1000:
Table of Contents

Advertisement

Technical specifications

10.2 5ST3 COM auxiliary switch and fault signal contact

10.2
5ST3 COM auxiliary switch and fault signal contact
Designation
Order number
Product name
Operating voltage rated value
Design of the product factory fitted
Available measurement data
Product expansion can be mounted
Number of modular width units
Product component auxiliary switch
Product component fault signal contact
IP degree of protection
Reference ID in accordance with IEC 81346-2:2009
Maximum operating voltage for DC
Minimum operating voltage for DC
Power loss [V_A] during standby
Maximum current consumption
Terminal type
Maximum connectable conductor cross-section
Minimum connectable conductor cross-section
Type of connectable conductor cross-sections with AWG
cables
Implementation of the LED display
Typical electrical endurance (operating cycles)
Maximum permissible ambient temperature during storage
Minimum permissible ambient temperature during storage
Minimum ambient temperature during operation
Maximum ambient temperature during operation
Height
Width
Depth
Net weight
Radio regulations EU
Radio transmission frequency
Radio transmission power
88
Value
5ST30620MC
5ST3 COM auxiliary switch / fault signal contact
24 V DC (SELV)
No
Manual ON/OFF, tripping operation, temperature, switching
cycles, operating hours, warnings
universal (LS, FI, FI/LS, AFDD ON/OFF 5TL1 remote operating
mechanism)
0.5
Yes
Yes
IP20
SF
28.8 V
19.2 V
0.5 W
20 mA
screwless
1.5 mm
2
0.2 mm
2
24 ... 16
Yes
10000
85°C
-40°C
-25°C
60°C
90 mm
9 mm
76.3 mm
28.5 g
2014/53/EU
2400 - 2483.5 MHz
2.5 dBm
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents