Chapter 9 Startup Using V-Tool
(3) Registering the remote side (FL654).
9
52
(a) Create the remote station folder.
Example: FL654 (model 2000)
(b) Register the base, FL654, and I/O modules.
(c) FL654 module parameter setting
IP address, the first address and the amount of transmission words of area1, the
first address and the amount of transmission words of area2 are set at this stage.
Because it needs it in "(5) the registering the talker blocks".
The amount of the transmission word in area 1 and area 2 is the values in which the
amount of the input module word and the I/O module status information (four words)
were added.
Model 2000 FL-net (OPCN-2) Remote I/O Station Module (FL654) User's Manual
Registration of the
remote side (FL654)