Chapter 9 Startup Using V-Tool
(7) Confirmation I/O variables
9
56
When I/O modules are registered, I/O variables are automatically registered.
When right-click on I/O module (for instance, DI635) with mouse pointer, and "I/O
variable" is selected, the I/O variable screen is displayed.
Please change on I/O variable screen when you change the variables.
However, because the I/O variables become network variables in FL654, the I/O
variables should apply a name unique on "FL-net ControlLAN".
The I/O variable registered automatically has unique name on "FL-net ControlLAN".
In this sample, the I/O variables have not changed.
I/O module
Automatic registered I/O variable identifier
DI633
IO01001_00000101
DO633
IO01001_00000102
DI635
IO01001_00000103
DO635
IO01001_00000104
AD628S
IO01001_00000105
DA672
IO01001_00000106
Notes of I/O variables registration
It is necessary to allocate network variables of FL654 by "Unit of the module" as "One
mass".
When the above-mentioned rule is not observed, the download of I/O configuration
information becomes an error (text parameter error).
Therefore, the variable is made an array type and it declares in the I/O variable
automatic registration.
Model 2000 FL-net (OPCN-2) Remote I/O Station Module (FL654) User's Manual
Data type
ARRAY[0..15] OF BOOL
ARRAY[0..15] OF BOOL
ARRAY[0..63] OF BOOL
ARRAY[0..63] OF BOOL
ARRAY[0..7] OF UINT
ARRAY[0..1] OF UINT