TZIDC, TZIDC-200 DIGITAL POSITIONER | COI/TZIDC/TZIDC-200-EN REV. B

3 Configuration

General information

Most parameters for the positioner can be set locally, meaning
that configuration only needs to be performed via the local
communication interface (LCI) or FSK modem and PC in
exceptional cases.
You may also deny or restrict local modification and saving of
parameters by completely or partially blocking access to the
configuration level
(see Chapter Locks on page 9 and the description of the
Funktionsauswahl parameter page 36).
To simplify the process, the different parameters are grouped as
follows:

Example

Parameter (1st line on the
Display (2nd line on the
display)
display)
P1._
STANDARD
P1.0
ACTUATOR
P1.1
AUTO_ADJ
P1.2
ADJ_MODE
P1.3
TEST
P1.4
EXIT
P2._
SETPOINT
ID
P1._
P2._
P3._
P4._
P5._
P6._
P7._
P8._
P9._
P10._
P11._
The following sections provide an overview (in tabular and
graphical format) of the overall structure of the parameter
groups and parameters.
Function
Possible parameter settings
Actuator type
LINEAR, ROTARY
Autoadjust
Command / Function is being run
Automatic adjustment mode
FULL, STROKE, CTRL, PAR,
ZERO_POS, LOCKED
Test
Command / Function is being run
Return to operating level
Command / Function is being run
Designator
Name
STANDARD
Standard
SETPOINT
Setpoint
ACTUATOR
Actuator
MESSAGES
Events
ALARMS
Alarms
MAN_ADJ
Manual adjustment
CTRL_PAR
Control parameters
ANLG_OUT
Analog output
DIG_OUT
Digital output
DIG_IN
Digital input
FS / IP
Factory setting, I/P-Type
Unit
Factory setting
LINEAR
FULL
INACTIV
NV_SAVE