TIME_OUT – stroke time monitoring
Use this parameter to activate the "Dead band time limit"
function.
The alarm is issued via digital output when the setpoint within
the specified monitoring time is not reached in control mode.
(The monitoring time is specified using parameter group 4
TIME-OUT). The function is only active in ACTUATOR and
AUTO_ADJ control modes.
ACTIVE
Dead band time limit is activated.
INACTIVE
Alarm not active.
STRK_CTR – Movement counter
With this parameter you can determine that an alarm is signaled
when the movement counter exceeds the specified limit value.
The limit value is edited remotely via PC.
ACTIVE
Alarm for exceeding travel counter limit value
INACTIVE
No Alarm
TRAVEL – travel counter
With this parameter you can determine that an alarm is signaled
when the travel counter exceeds the specified limit value. The
limit value is edited remotely via PC.
ACTIVE
Alarm for exceeding movement counter limit value
INACTIVE
No Alarm
EXIT – Back to work level
With this parameter you can leave the configuration level. The
positioner returns to the operating level. Here you can either
save data in the non-volatile memory or discard all previously
made changes (also the changes in other parameter groups).
To exit the configuration level (with or without saving), press
and hold the ENTER button, until the countdown has run from 3
to 0 and finished.
The active saving process is indicated by the message NV_SAVE.
After saving a plausibility check is executed.
If an error occurs during the check or while saving, the data
cannot be saved and an error message is displayed instead (see
Chapter Error codes on page 40).
Selection
NV_SAVE
Saves settings in the non-volatile memory.
CANCEL
Discards all changes made since the last permanent
save operation.