TZIDC, TZIDC-200 DIGITAL POSITIONER | COI/TZIDC/TZIDC-200-EN REV. B
EXIT – Back to work level
With this parameter you can leave the configuration level. The
positioner returns to the operating level. Here you can either
save data in the non-volatile memory or discard all previously
made changes (also the changes in other parameter groups).
To exit the configuration level (with or without saving), press
and hold the ENTER button, until the countdown has run from 3
to 0 and finished.
The active saving process is indicated by the message NV_SAVE.
After saving a plausibility check is executed.
If an error occurs during the check or while saving, the data
cannot be saved and an error message is displayed instead (see
Chapter Error codes on page 40).
Selection
NV_SAVE
Saves settings in the non-volatile memory.
CANCEL
Discards all changes made since the last permanent
save operation.

Parameter group 11: Safety position

FAIL_POS – Safety position
This parameter needs to be used to activate the safety position,
if the factory settings are loaded ( FACT_SET parameter) or the
I/P module type is changed (IP-TYP parameter).
Note
After setting parameters FACT_SET and IP-TYP as required, the
safe position must be deactivated again manually.
The safe position that is activated (i.e., whether the actuator is
ventilated or blocked) depends on the I/P module installed.
Activating / deactivating the safe position:
Press and hold the ENTER button, until the countdown displayed
on it has run from 3 to 0 and finished; then release the ENTER
button.
The safe position is activated or deactivated, respectively.
37