Item
Input signal voltage
Input impedance
Input signal current
Input sensitivity
current
Input response time
Input signal type
Circuit insulation
Indication of input motion
*1.
If inputs X000 to X005 are assigned to the zero-phase signal of the DSZR instruction or the near-point
signal (DOG) of the ZRN instruction, the input response time will be as shown in the following table.
1. Internal input circuit
1) AC power type
Sink input type
Main unit
PLC User's Manual - Positioning Control Edition
All inputs
X000 to X007
X010 to X017
X000 to X007
X010 to X017
X000 to X007
Input ON
current
X010 to X017
Input OFF
All inputs
current
All inputs
All inputs
All inputs
All inputs
Input
Input response time
X000, X001
X002 to X005
Fuse
Class-D
grounding
Input
impedance
Series main unit. Note that the simultaneous
3S
Refer to the FX
24 V DC input specifications
AC power type: 24 V DC ±10%
DC power type: 20.4 to 26.4 V DC
7 mA/24 V DC
5 mA/24 V DC
4.5 mA or more
3.5 mA or more
1.5 mA or less
Approx. 10 ms
No-voltage contact input
NPN/PNP open collector transistor
Photocoupler insulation
Turning on the input will light the LED indicator lamp
10 s
50 s
Source input type
Main unit
2 Specifications
2.4 Input Specifications
Hardware Edition.
3S
3.3 k
4.3 k
*1
Fuse
Class-D
grounding
Input
impedance