LG ACHH017VBAB Installation And Owner's Manual page 22

Air-cooled inverter scroll heat pump chiller
Table of Contents

Advertisement

REFRIGERANT PIPING AND SENSOR DIAGRAM /
OPERATION RANGE AND LIMIT
ACHH Chilled Water Operation Limits and Performance
105
95
85
75
65
55
45
35
25
15
5
5
15
Cold Water Inlet
Temperature F
Cold Water Outlet
Temperature F
Ambient Range
Approved Δ between EWT and LWT is 4°F to 20°F
100%
90%
80%
70%
68°F LWT (100% to 65%)
60%
44°F LWT (100% to 50%)
50%
14°F LWT (77% to 33%)
40%
30%
5
15
22
25
35
45
Ambient Air Degrees F
18°F to 88°F
14°F to 68°F
5°F to 125°F
Cooling Capacity Performance 10°ΔT (EWT to LWT)
25
35
45
Ambient Air Degrees F
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
55
65
75
85
1. Proper Glycol Solution is required for LWT at
or below 32°F.
2. Proper Glycol Solution is required for Ambient
Operation at or below 41°F
3. Operation Limit Recommendation for 208-230V
is 120°F.
4. LG LATS ISC Selection Software is to be used to
confirm selection and performance.
55
65
75
85
95
105
115
125
95
105
115
125

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents