• Edit Unit Address
In the device mode, if you press Edit Unit Address area, the Edit Unit Assress window is dis-
played.
If you press Edit Unit Count area, a window to set count of chillers appears.
Select from 1 to 5, Count of chillers to interface, and press Apply button.
If Cancel is pressed, the previous setting is maintained.
Default value is 1, and you can set and use up to 5.
Setting product address The product address must be in both main PCB of unit and HMI.
If the two addresses are not the same, there will be an error in HMI communication.
CAUTION
!
If you reset the address in HMI while the product is operating, it will cause a communication
error and stop the product. Aiways reset the address after the product has stopped com-
pletely.
Due to our policy of continuous product innovation, some specifications may change without notification.