LG ACHH017VBAB Installation And Owner's Manual page 24

Air-cooled inverter scroll heat pump chiller
Table of Contents

Advertisement

REFRIGERANT PIPING AND SENSOR DIAGRAM /
OPERATION RANGE AND LIMIT
20 TON Module Heating
Performance Maximum
LWT / Minimum Ambient
237.8 MBH
235.1 MBH
221.9 MBH
208.7 MBH
195.5 MBH
178.2 MBH
152.2 MBH
143.3 MBH
135.0 MBH
139.7 MBH
145.0 MBH
141.6 MBH
125.9 MBH
86.5 MBH
71.3 MBH
86°F LWT COP 1.30
-22 -20 -15 -10 -5
1.
The performance chart above is based on a ACHH020*BAB operating at maximum
allowable capacity for the speci c conditions.
2.
The 40 Ton ACHH040*BAB will provide 2X the capacity at the same conditions.
3.
The 60 Ton ACHH060*BAB will provide 3X the capacity at the same conditions.
4.
LATS ISC is a dynamic selection tool provided in support of the LG ACHH Series
Inverter Scroll Heat Pump Chiller. Please refer to LATS for nal and speci c
performance data.
5.
The chart above is intended only to be used as a guide tool. Selection done in LATS.
6.
LG reserves the right to alter performance values at any time.
24
124°F LWT COP 1.60
120°F LWT COP 1.49
113°F LWT COP 1.45
106°F LWT COP 1.41
100°F LWT COP 1.37
90°F LWT COP 1.37
86°F LWT COP 1.33
0
5
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
131°F LWT COP 2.52
131°F LWT COP 2.36
131°F LWT COP 2.21
131°F LWT COP 2.06
131°F LWT COP 1.91
131°F LWT COP 1.76
131°F LWT COP 1.70
Ambient Temperature Degrees F

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents