OPTIONAL SETTINGS
Description
Start/Stop
Cooling/Heating
Cooling setpoint tem-
perature
Heating setpoint tem-
perature
Load outflow water
Temperature
Control Mode
Remote Mode
Central Control
Address
Maximum Operation
Frequency
Capacity of product
Version
44
Screen Display
(1 Level)
Set RUN to operate the product and STOP to stop the
RUN /STOP
operation.
Sets the product's Cooling/Heating Operation Mode.
HEAT/COOL
COOL selects Cooling Mode and HEAT selects Heat-
ing Mode.
7
Sets Cooling Target Temperature. (4 °C~ 20 °C)
45
Sets Heating Target Temperature.(30 °C~ 55 °C)
Shows the temperature value of Load outflow water.
-
(Specified in 0 Level)
Set's the product's Control Mode. In LOC, the product
control is available with HMI and Chiller Controller.
LOC/DIST/SCHE
DIST refers Remote Control Mode. In SCHE, the prod-
uct is controlled following the schedule set at HMI.
Sets how to set in Remote Mode. CONT enables the
product's operation mode by simple switch contacts.
CONT/BUS
BUS enables the control on the entire product through
communication from other communication devices.
The product address can be set for communication
1
with other communication devices. The address can
be set by selecting values from 1-247.
Sets the Maximum Operation Frequency.(70 Hz~130
110
Hz)
Shows the current Capacity of product.
-
(Specifies in 0 Level)
Shows the program information of Chiller Controller
installed in the current product as Version. Version
-
information is subjected to change for improvement of
the product performance or the quality improvement.
(Specifies in 0 Level)