Oxley Creek WWTP Water Reclamation
(Probe LU Manual) Vendor Manual
3.1.6. Process Value Scale
3.1.6.1. Lower Value (default 0)
3.1.6.2. Upper Value (default 100)
3.1.7. Output Scale
3.1.7.1. Lower Value (default 0)
3.1.7.2. Upper Value (default 100)
3.1.8. Output Limits
3.1.8.1. Lower Limit Alarm
3.1.8.2. Lower Limit Warning
3.1.8.3. Upper Limit Warning
3.1.8.4. Upper Limit Alarm
Page 98
SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL
Defines the operational lower range value of the input value (Process
Value Scale) in engineering units. Process Value Scale normalizes the
input value to a customer-defined range.
Defines the operational upper range value of the input value (Process
Value Scale) in engineering units. Process Value Scale normalizes the
input value to a customer-defined range.
6
5
4
3
2
1
0
1
2
Scales the Process Variable. The function block parameter OUT SCALE
contains the values of the lower limit and upper limit effective range.
Defines the operational lower range value of the output value in
engineering units.
Defines the operational upper range value of the output value in
engineering units.
The setting for the lower alarm limit in engineering units.
The setting for the lower warning limit in engineering units.
The setting for the upper warning limit in engineering units.
The setting for the upper alarm limit in engineering units
Out (AIFB1 or AIFB2 Out)
3
4
5
Doc Id: VM11
Active Date: 15/12/2006
7ML19985JB02