Precautions:
Avoid proximity to high voltage or current wiring, high voltage or current contacts,
and to variable frequency motor speed controllers.
Avoid interference to the sound path from obstructions or from the fill path
The sound path should be:
perpendicular to the
monitored surface
clear of rough walls,
seams, rungs, or
other obstructions
clear of the fill path
M ounting Instructions
Note:
Ideally, mount SITRANS Probe LU so that the face of the transducer is at least 300
mm (1 ft) above the highest anticipated level.
SITRANS Probe LU is available in three thread types:
2" NPT
2" BSP
PF2/G (BS EN ISO 228-1)
1.
Before inserting SITRANS Probe LU into its mounting connection, ensure that the
threads are of the same type to avoid damaging them.
2.
Simply screw SITRANS Probe LU into the process connection and hand tighten.
Page 12
SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL
Doc Id: VM11
Active Date: 15/12/2006
pipe
ladder
rungs
seam
7ML19985JB02
Fill
10 °