Appendix B: Troubleshooting

1.
Check the following:
There is power at the instrument.
The LCD shows the relevant data.
Check whether any fault codes are being displayed (see
Diagnostics (General Fault Codes)
The device can be programmed using the handheld programmer.
2.
Verify that the wiring connections are correct.
3.
Check the PROFIBUS address and make sure all devices are at unique PROFIBUS
addresses.
4.
If you are unable to program the device via the handheld programmer, make sure
local operation is enabled (see
that Write Locking is Off (see
5.
If you try to set a SITRANS Probe LU parameter via remote communications, but the
parameter remains unchanged, make sure remote operation is enabled (see
Remote operation enable
Write Locking
6.
If you continue to experience problems, go to our website at www.siemens.com/
processautomation, and check the FAQs for SITRANS Probe LU, or contact your
Siemens Milltronics representative.
7.
If the PLC value equals the display value, but does not correspond to actual material
level, either:
scaling in AIFB1 is incorrect, or
High Calibration Point is incorrectly entered, or
the wrong echo is being selected.
8.
If the PLC value is not equal to the displayed value (regardless of actual material
level), either:
you may not be looking at the right spot in the PLC, or
you may have programmed scaling into the PLC, instead of leaving all scaling to
be performed in the Probe LU, or
the PCL may not be communicating with the Probe LU. Check the network to
verify that you are communicating.

General Fault Codes

For a table listing the fault codes, meanings, and suggested corrective action to take,
please see
Page 40
SITRANS Probe LU (PROFIBUS PA)– INSTRUCTION MANUAL
on page 45). Also make sure that Write Locking is Off (see
on page 76).
Acyclic Extended Diagnostics (General Fault Codes)
on page 30 for a detailed list).
Local operation enable
Write locking
on page 45).
Doc Id: VM11
Active Date: 15/12/2006
Acyclic Extended
on page 44). Also make sure
on page 30.