2.3. Standard Setup

2.3.1. Response Rate
Sets the reaction speed of the device to measurement changes in the target
range.
Related
para-
meters
Hand
programmer
values
Note:
Fill Rate, Empty Rate, and Echo Lock.
Use a setting just faster than the maximum filling or emptying rate (whichever is
greater). Slower settings provide higher accuracy: faster settings allow for more
level fluctuation.
2.3.2. Echo Lock
Note:
monitoring the vessel, to avoid stationary blade detection.
Selects the measurement verification process.
Hand programmer
values
Related parameters
If a material agitator or mixer is used in the monitored vessel, Echo Lock should
be set for Maximum Verification or Material Agitator to avoid agitator blade
detection.
1.
For more detail, see
2.
For more detail, see
Page 78
SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL
12
Response
Rate
slow
medium
fast
Changing Response Rate resets the following parameters: LOE Timer,
Ensure the agitator is always running while SITRANS Probe LU is
Maximum Fill Rate
Maximum Empty Rate
Echo Lock Sampling
Echo Lock Window
Algorithm
LOE Timer
on page 36.
Echo Lock
on page 35.
1
LOE Timer
Fill Rate
(minutes)
m/minute
m/minute
m/minute
Off
Maximum Verification
Material Agitator
Total Lock
Doc Id: VM11
Active Date: 15/12/2006
Echo
Empty
2
Rate
Lock
m/minute
m/minute
m/minute
7ML19985JB02